Digital electronic modules
3.20 2RO NO/NC 24 VDC to 48 VDC/5 A, 24 VAC to 230 VAC/5 A digital electronic module (6ES7132-4HB11-
0AB0)
ET 200S
3-86
Manual, Edition 10/2005, A5E00514527-01
Switching capacity and lifetime of the contacts
With an external protective circuit, the contacts will last longer than specified in the table.
The normally open and normally closed contacts of the relay have a different lifetime. The
table shows the switching capacity and lifetime of the contacts.
Table 3-6
Switching capacity and lifetime of the contacts
Resistive load
Voltage
Current
Duty cycles (typ.)
Normally closed
contact
Duty cycles (typ.)
Normally open
contact
5.0 A
0.1 million
0.15 million
4.0 A
0.2 million
0.175 million
2.0 A
0.45 million
0.3 million
0.5 A
1.4 million
1.1 million
24 VDC
0.1A
1.5 million
1.5 million
2.0 A
0.15 million
0.11 million
1.0 A
0.3 million
0.2 million
0.5 A
0.6 million
0.6 million
48 VDC
0.1A
0.8 million
0.6 million
48 VAC
2.0 A
0.45 million
0.35 million
60 VAC
2.0 A
0.45 million
0.35 million
5.0 A
0.1 million
0.1 million
3.0 A
0.2 million
0.2 million
2.0 A
0.4 million
0.3 million
1.0 A
0.8 million
0.6 million
120 VAC
0.5 A
1.5 million
1.0 million
5.0 A
0.1 million
0.1 million
3.0 A
0.2 million
0.2 million
2.0 A
0.4 million
0.3 million
1.0 A
0.8 million
0.6 million
For resistive load
230 VAC
0.5 A
1.5 million
1.0 million
2.0 A
0.1 million
0.1 million
1.0 A
0.2 million
0.2 million
24 VDC
0.5 A
0.5 million
0.5 million
2.0 A
0.07 million
0.05 million
1.0 A
0.15 million
0.1 million
For inductive load in
accordance with IEC
947-5-1 DC 13/ AC
15
48 VDC
0.5 A
0.4 million
0.25 million
48 VAC
1.0 A
0.5 million
0.3 million
60 VAC
1.0 A
0.5 million
0.3 million
2.0 A
0.1 million
0.1 million
1.0 A
0.3 million
0.1 million
0.5 A
0.9 million
0.6 million
120 VAC
0.1 A
1.5 million
1.0 million
2.0 A
0.1 million
0.1 million
1.0 A
0.5 million
0.3 million
0.5 A
0.9 million
0.6 million
230 VAC
0.1 A
1.0 million
1.0 million