Analog electronic modules
4.2 Analog value representation
ET 200S
Manual, Edition 10/2005, A5E00514527-01
4-13
Measuring range for thermocouple type T
Table 4-22 SIMATIC S7 format: Measuring range Type T in °C and °F
Units
Units
Type T in °C
Decimal Hexadecima
l
Type T in °F
Decimal
Hexadeci
mal
Range
> 540.0
32767
7FFF
H
> 1004.0
32767
7FFF
H
Overflow
540.0
:
400.1
5400
:
4001
1518
H
:
0FA1
H
1004.0
752.1
10040
7521
2738
H
1DC1
H
Overshoot range
400.0
:
-270.0
4000
:
-2700
0FA0
H
:
F574
H
752.0
:
-454.0
7520
:
-4540
1D60
H
:
EE44
H
Rated range
< -270.0
-32768
8000
H
< -454.0
-32768
8000
H
Underflow
4.2.6
Output ranges of the analog output modules in SIMATIC S7 format for voltage and
current
Output modules for voltage and current: ± 5 V; ± 10 V; ± 20 mA
Table 4-23 SIMATIC S7 format: output range ± 5 V; ± 10 V; ± 20 mA
Units
Output range
± 5 V
Output range
± 10 V
Output range
± 20 V
Decimal
Hexadecima
l
Range
0
0
0
> 32511
> 7EFF
H
Overflow
5.8800
:
5.0002
11.7589
:
10.0004
23.5150
:
20.0007
32511
:
27649
7EFF
H
:
6C01
H
Overshoot range
5.0000
3.7500
:
- 3.7500
- 5.0000
10.0000
7.5000
:
- 7.5000
- 10.0000
20.0000
14.9980
:
- 14.9980
- 20.0000
27648
20736
:
-20736
-27648
6C00
H
5100
H
:
AF00
H
9400
H
Rated range
- 5.0002
:
- 5.8800
- 10.0004
:
- 11.7589
- 20.0007
:
- 23.5160
-27649
:
-32512
93FF
H
:
8100
H
Undershoot range
0
0
< - 23.5160
< -32512
< 8100
H
Underflow