Analog electronic modules
4.2 Analog value representation
ET 200S
4-8
Manual, Edition 10/2005, A5E00514527-01
Measuring ranges for resistance thermometer Ni x00 Climatic
Table 4-11 SIMATIC S7 format: Measuring ranges Ni 100, 120, 200, 500, 1000 Climatic in °C and °F
Units
Units
Ni x00 Climatic in °C
(1 digit = 0.01 °C)
Decimal Hexadecima
l
Ni x00 Climatic in °F
(1 digit = 0.01 °F)
Decimal
Hexadeci
mal
Range
> 295.00
32767
7FFF
H
> 325.11
32767
7FFF
H
Overflow
295.00
:
250.01
29500
:
25001
733C
H
:
61A9
H
327.66
:
280.01
32766
:
28001
7FFE
H
:
6D61
H
Overshoot range
250.00
:
-60.00
25000
:
-6000
61A8
H
:
E890
H
280.00
:
-76.00
28000
:
-7600
6D60
H
:
E250
H
Rated range
-60.01
:
-105.00
-6001
:
-10500
E88F
H
:
D6FC
H
-76.01
:
-157.00
-7601
:
-15700
E24F
H
:
C2AC
H
Undershoot
range
< -105.00
-32768
8000
H
< -157.00
-32768
8000
H
Underflow
Measuring ranges for resistance thermometer Cu 10 Standard
Table 4-12 SIMATIC S7 format: Measuring ranges Cu 10 Standard in °C and °F
Units
Units
Cu 10 Standard in °C
(1 digit = 0.1 °C)
Decimal Hexadecima
l
Cu 10 Standard in °F
(1 digit = 0.1 °F)
Decimal
Hexadeci
mal
Range
> 312.0
32767
7FFF
H
> 593.6
32767
7FFF
H
Overflow
312.0
:
260.1
3120
:
2601
C30
H
:
A29
H
593.6
:
500.1
5936
:
5001
1730
H
:
12D5
H
Overshoot range
260.0
:
-200.0
2600
:
-2000
A28
H
:
F830
H
500.0
:
-328.0
5000
:
-3280
1389
H
:
F330
H
Rated range
-200.1
:
-240.0
-2001
:
-2400
F82F
H
:
F6A0
H
-328.1
:
-400.0
-3281
:
-4000
F32F
H
:
F060
H
Undershoot
range
< -240.0
-32768
8000
H
< -400.0
-32768
8000
H
Underflow