Analog electronic modules
4.5 Parameters for analog electronic modules
ET 200S
Manual, Edition 10/2005, A5E00514527-01
4-27
See also
Connecting Thermocouples (Page 4-18)
4.5.2
Parameters for analog electronic modules 2AI U High Feature and 2AI I 2/4WIRE
High Feature
Table 4-31 Parameters for analog electronic modules U, I High Feature
2AI U High Feature
2AI I 2/4WIRE High Feature
Range of values
Default setting
Applicability
Group diagnosis (parameter assignment error,
internal error)
•
disable
•
Enable
disable
Module
Diagnostics: Overflow/underflow
•
disable
•
Enable
disable
Module
---
Diagnostics: Wire break
1
•
disable
•
Enable
disable
Channel
Smoothing
•
None
•
Weak
•
Medium
•
Strong
None
Channel
Type/range of
measurement
---
•
De-activated
•
± 5 V
•
1 V to 5 V
•
± 10 V
± 10 V
Channel
---
Type/range of measurement
•
De-activated
•
4 to 20 mA
•
± 20 mA
4 to 20 mA
Channel
Interference frequency suppression
•
disable
•
Enable
disable
Module
Run-time calibration
•
disable
•
Enable
disable
Module
1
Only in the measuring range 4 to 20 mA
See also