Analog electronic modules
4.5 Parameters for analog electronic modules
ET 200S
4-32
Manual, Edition 10/2005, A5E00514527-01
Type of measurement
The following table lists the temperature coefficients and measuring ranges you can set for
each measurement type:
Type of measurement
Temperature coefficient
Measuring range
De-activated
–
–
Four-wire resistor
Three-wire resistor
–
150 Ω / 300 Ω / 600 Ω / 3000 Ω
Two-wire resistor
–
150 Ω / 300 Ω / 600 Ω / 3000 Ω / PTC
Pt 0.003850/ Pt 0.003916 /
Pt 0.003902 / Pt 0.003920 /
Pt 0.003851
1
Pt100 climatic range /
Pt100 standard range /
Pt200 climatic range /
Pt200 standard range /
Pt500 climatic range /
Pt500 standard range /
Pt1000 climatic range /
Pt1000 standard range
Ni 0.006180
1
/ Ni 0.006720
Ni100 climatic range /
NI100 standard range /
Ni120 climatic range /
Ni120 standard range /
Ni200 climatic range /
Ni200 standard range /
Ni500 climatic range /
Ni500 standard range /
Ni1000 climatic range /
Ni1000 standard range
Ni 0.005000
Ni 1000 climatic range
2
Ni 1000 standard range
2
Three-wire thermal resistor
Cu 0.00427
1
Cu10 climatic range /
Cu10 standard range
Pt 0.003850 / Pt 0.003916 /
Pt 0.003902 / Pt 0.003920 /
Pt 0.003851
Pt100 climatic range /
Pt100 standard range /
Pt200 climatic range /
Pt200 standard range /
Pt500 climatic range /
Pt500 standard range /
Pt1000 climatic range /
Pt1000 standard range
Ni 0.006180 / Ni 0.006720
Ni100 climatic range /
Ni100 standard range /
Ni120 climatic range /
Ni120 standard range /
Ni200 climatic range /
Ni200 standard range /
Ni500 climatic range /
Ni500 standard range /
Ni1000 climatic range /
Ni1000 standard range
Two-wire thermal resistor
Four-wire thermal resistor
Ni 0.005000
Ni 1000 climatic range
2
Ni 1000 standard range
2
1
The default settings for the temperature coefficients are valid for Europe.
2
For LG-Ni 1000 sensors from Siemens Building Ltd (Landis & Stäfa)