Digital electronic modules
3.15 2DO 24 VDC/2 A Standard digital electronic module (6ES7132-4BB31-0AA0)
ET 200S
3-60
Manual, Edition 10/2005, A5E00514527-01
Lamp load
max. 2.5 W
Connecting two outputs in parallel
•
For redundant triggering of a load
Yes (per module)
•
To increase performance
no
Control of a digital input
Yes
Switch rate
•
For resistive load
100 Hz
•
On inductive load
2 Hz
•
For lamp load
10 Hz
Limitation (internal) of the voltage induced on
circuit interruption
Typically L+ (-55 V to -60 V)
Reverse-voltage proof
Yes, if using the same load voltage as at the
power module
Short-circuit protection of the output
Yes
2
•
Threshold on
Typically 1.5 A
1
Polarity reversal can lead to the digital outputs being connected through.
2
Per channel
3.15
3.15
2DO 24 VDC/2 A Standard digital electronic module
(6ES7132-4BB31-0AA0)
Properties
•
Digital electronic module with two outputs
•
Output current 2 A per output
•
Rated load voltage 24 VDC
•
Short-circuit protection
•
Suitable for solenoid valves, DC contactors, and indicator lights
Peculiarity
When you connect the 24 VDC rated load voltage to the power module by means of a
mechanical contact, depending on the circuit the digital outputs carry the "1" signal for
approximately 50 µs. You need to take this into account if you connect the module to fast
counters.