Digital electronic modules
3.19 2RO NO 24 VDC to 120 VDC/5 A, 24 VDC to 230 VAC/5 A digital electronic module (6ES7132-4HB01-0AB0)
ET 200S
Manual, Edition 10/2005, A5E00514527-01
3-81
Switching capacity and lifetime of the contacts
With an external protective circuit, the contacts will last longer than specified in the table.
This table shows the switching capacity and endurance of the relay contacts:
Table 3-5
Switching capacity and lifetime of the relay contacts
Resistive load
Voltage
Current
Operating cycles
(typical)
5.0 A
0.1 million
4.0 A
0.2 million
2.0 A
0.5 million
1.0 A
1.6 million
0.5 A
4 million
24 VDC
0.1A
7 million
60 VDC
0.5 A
1.6 million
120 VDC
0.2 A
1.6 million
48 VAC
2.0 A
1.6 million
60 VAC
2.0 A
1.2 million
5.0 A
0.1 million
3.0 A
0.2 million
2.0 A
0.4 million
1.0 A
0.8 million
120 VAC
0.5 A
1.5 million
5.0 A
0.1 million
3.0 A
0.2 million
2.0 A
0.4 million
1.0 A
0.8 million
For resistive load
230 VAC
0.5 A
1.5 million
2.0 A
0.1 million
1.0 A
0.2 million
24 VDC
0.5 A
0.5 million
60 VDC
0.5 A
0.2 million
120 VDC
0.2 A
0.5 million
48 VAC
1.0 A
0.7 million
60 VAC
1.0 A
0.5 million
2.0 A
0.1 million
1.0 A
0.3 million
0.5 A
1 million
For inductive load in
accordance with IEC
947-5-1 DC 13/ AC 15
120 VAC
0.1A
2 million
2.0 A
0.1 million
1.0 A
0.3 million
For inductive load in
accordance with IEC
947-5-1 DC 13/ AC 15
230 VAC
0.5 A
1 million