4 IQ-SENSE (6ES7138-4GA00-0AB0)
ET 200S
Manual, Edition 10/2005, A5E00514527-01
5-3
Parameters
Range of values
Default setting
Applicability
Time value
•
5 ms
•
10 ms
•
20 ms
•
50 ms
•
100 ms
•
200 ms
•
500 ms
•
1 s
•
2 s
•
5 s
•
10 s
5 ms
Channel
Teach-in disable
•
Teach-in
with button
possible
•
Teach-in
with button not
possible
Teach-in
with button
possible
Channel
Note
Unused channels of the module must be deactivated otherwise the wire break diagnosis will
be reported.
Measurement type parameter: De-activated
•
All the diagnostics are suppressed.
•
Sensitivity/distance values and circuit states are set to "0".
•
The sensor is switched off.
5.2.2
Group diagnostics parameter
If group diagnostics is enabled, a pending diagnostics message is entered.
Reference
Information on channel-related diagnostics can be found in the
ET 200S Operating
Instructions.
5.2.3
Synchronization group parameter
•
Sensors between different modules of the 4 IQ-SENSE may influence one another (e.g.
scattered light).
•
To prevent interference from neighboring sensors on different modules, this parameter
can be used to allocate a separate synchronization group to every module. Modules in
different synchronization groups do not interfere with one another.
•
Sensors on the same module cannot interfere with one another.