RESERVE modules
ET 200S
6-2
Manual, Edition 10/2005, A5E00514527-01
Note
If you use RESERVE modules:
•
The SF LED lights up on the interface module
•
A channel-specific diagnostic and module status "10
B
: Wrong module" are reported
for the RESERVE module slot.
Pin assignment
The RESERVE module has no connection to the terminals of the TM-E terminal module.
This enables you to fully wire the TM-E terminal module and prepare it for the subsequent
application.
RESERVE Module Technical Specifications (6ES7138-4AAx1-0AA0)
Dimensions and Weight
Dimension W x H x D (mm)
Weight
15 x 81 x 52
30 x 81 x 52
Approx. 33 g (installation width 15 mm)
Approx. 55 g (installation width 30 mm)
Voltages, currents, potentials
Power dissipation of the module
Typically 0.025 W
Status, interrupts, diagnostics
Status display
no
Diagnostics function
no
Note
The address space must correspond with the address space of the planned electronic
module.
Reference
For information on the option handling and implementation of RESERVE modules can be
found in the
ET 200S Operating Instructions in Functions > Option Handling on the