5
5.9 Memory Management
110
Power Meter SICAM P 7KG7750/55, Manual
E50417-B1076-C340-A6, Edition 09.2013
Binary states
Calculation example
with 20 % memory size
5.9.2
Mean Values
In this dialog window you can specify the settings for mean value recording.
Proceed as follows:
1. Select up to eight
Measured values
and
Test points
.
2. Select a
Date
or one of the six
Limit value group
s as
Start selector
for the average value
recording. It is possible to combine Date and Limit value group as start selectors. The first of
the two criteria fulfilled, will launch the recording.
3. When entering a date as
Start selector
, you must indicate a year between 2000 and 2060.
4. The
Ring buffer
mode allows you to select, if the oldest values will be overwritten (=
Yes
) or
not (=
No
) when the capacity of the associated memory area is exhausted.
Byte
Byte
emory
AllocatedM
Values
8
]
[
=
209715 Byte
8 Byte
Values =
= 26214