6 Connection Principle
6.3 Connection Types and Connection Examples
90
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Example 3-wire Network, 2 Voltage Transformers and 2 Current Transformers, Unbalanced
Figure 6-7
Example 3-wire Network, 2 Voltage Transformers and 2 Current Transformers, Unbalanced
a
b
P1
P2
S1
S2
c
A
A
B
B
a
a
b
b
P1
P2
S1
S2
PE
10 A
10 A
10 A
Terminals SENTRON PAC5100/5200
NOTICE
The secondary voltage on terminal F (voltage) must not exceed AC 480 V (AC 347 V for UL conditions).
Non-observance can cause material damage.
✧
Make sure that the maximum permissible phase-to-ground voltage (PE) is not exceeded.