7 Operation at Use of a PC
7.3 Configuration of the Device
143
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
7.3.5.4 Memory Management
Default Settings and Setting Ranges
1)
The memory sizes for event list, PQ records and fault records can be changed.
2)
The memory size for trend recording is calculated automatically and forms the difference to 100 % of the
total memory size. The maximum total memory size of 100 % cannot be exceeded due to
parameterization errors.
3)
If the rest storage capacity fall below 31 %, it will mark as red color on User Interface, then the activation
is not possible.
To change the memory management, proceed as follows:
Table 7-14
Memory Management
Parameter
Default Setting
Setting Range
Splitting
Event recorder
1.0 %
1 % to 33 %
1)
Measurement recorder
35.0 %
(the recording time depends on
the aggregation interval)
33 % to 65 %
1)
Trend recorder
61.0 %
(residual storage capacity)
31 % to 63 %
2) 3)
Fault recorder
3.0 %
(Numbers of records depends on
the fault record time.)
3 % to 35 %
1)
NOTE
When the device has been recording data for a longer period already, a modification of the memory areas might
lead to the following message:
„
Memory size should not be changed now. If you active changes, all PQ data will be lost. Please backup data
before activation or cancel changes.
”
This message is only output if the stored data and the data to be expected exceed the storage capacity of the
SD card.