7 Operation at Use of a PC
7.3 Configuration of the Device
138
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
7.3.5.3 Recorder Parameters
Default Settings and Setting Ranges
1)
The trend recorder also creates a PQDIF file when 1024 data points (voltage values with a time stamp)
have been generated within the recording interval.
Table 7-12
Recorder Management
Parameter
Default Setting
Setting Range
Measurement Recorder
Average intervals - Frequency
10 s
fixed
Short term flicker
10 min
fixed
Long term flicker
2 h
fixed
Average interval - Voltage /
Unbalance / Harmonics
10 min
30 s, 1 min, 10 min, 15 min, 30 min,
1 h, 2 h
Record additional data (I, P, Q,
S etc.)
no
no
yes
Recorder of average - Min
no
no
yes
Recorder of average - Max
no
no
yes
Harmonics
Odd
Even
Odd
All
File generation every:
(corresponds to the setting of
the
Average interval
parame-
ter)
The created PQDIF files can be
downloaded via the User Inter-
face.
24 h
File generation
every:
At average interval
1 h (fix)
30 s
2 h (fix)
1 min
2 h
10 min, 15 min,
30 min, 1 h or
2 h
4 h
6 h
12 h
24 h
Recorded file type
PQDIF
PQDIF (see chapter 7.4.2.4)
CSV
All
Flicker lamp model
230 V
230 V
120 V
Trend Recorder
Tolerance unit
Percentage
Percentage
Numerical
Tolerance number
Percentage: 3 % of declared
input voltage Udin,
Numerical: 0.50 V
1 % to 5 % in 1 % steps
0.2 V to 500.0 V
Maximum recording interval
10 min
10 min, 30 min, 1 h, 2 h, 4 h, 6 h,
12 h, 24 h
1)