7 Operation at Use of a PC
7.3 Configuration of the Device
140
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
The Measured Value Recorder Intervals and the PQDIF Files
The measurement value recorder is responsible for recording average values, min and max values.
The measured values recorder intervals are defined according to the averaging intervals setting.
Table 7-13
PQDIF File Interval (measured value recorder)
Set
averaging
interval
Recording
duration for
creating a PQDIF
file
Time at start of
recording of a
complete PQDIF file
Start of recording (recorder start option)
30 s
1 h
00:00 h
01:00 h
02.00 h
....
22:00 h
23:00 h
- start at the next minute limit
- start at the next 10-minute limit
- immediate start
- start at the next hour limit
- start next day
1 min
2 h
00:00 h
02:00 h
04.00 h
....
20:00 h
22:00 h
10 min
2 h, 4 h, 6 h, 12 h
oder 24 h
15 min
30 min
1 h
2 h