14 Operating Parameters
14.1 Process Connections
246
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Operating mode
(only if source type = indication)
Persistent
Persistent
Persistent with fail safe
Pulse
Pulse with retrigger
Energy increase per pulse
(only if source type = energy coun-
ter)
1.0 Wh
0.1 Wh/VAh/varh to
1 000 000 Wh/VAh/varh
Output time pulse operating mode
(only if source type = indication and
pulse output or pulse output with re-
trigger or if source type = energy
meter)
20 * 10 ms = 200 ms
50 ms to 3 600 000 ms
Parameter
Default Settings
Setting Range