7 Operation at Use of a PC
7.3 Configuration of the Device
148
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
✧
If you do not want to make any additional settings, continue with the
Activation
of the device configuration
Activating the Set of Parameters
. If you want to change other settings, enter the
changes and then enable the device configuration as described in section
.
Depending on the parameterized
Start record option
, the
Start time
field shows the start time of the
recording. After activation, the recording starts automatically at the specified time. If the
Start immediately
option is selected, the recording also only starts after activation.
After recording has started, the
Recording status
fields shows the entry
Running
.
✧
If you want to stop the recording, click on
Stop recording
and execute the activation.
The
Recording status
field shows the entry
Not running
and
Start recording
is displayed on the user
interface.
Recording Power Quality Data
When the device is started for the first time, it is necessary for the recording of power quality data that the
Time
synchronization
of the device is set to the current time first. If the time is incorrect, the power quality measure-
ments do not conform to the current time. Proceed as follows:
✧
Refresh the time via
Ethernet NTP
or
Field bus
in line with Time Synchronization or with the device-
internal
clock in line with Date/Time.
✧
Configure all necessary parameters (for example, AC measurement, Communication, etc.) on the relevant
tabs,
except for
the
Recording parameters
settings.
When setting the parameters, make sure that the settings are consistent with each other (for example,
setting of the flicker lamp model consistent with the primary nominal voltage).
✧
At last
, parameterize the
Recording parameters
and activate the settings.
NOTE
The restart of the record is carried out after a power failure automatically.
The status will change from
Not running
to
Running
when user change and activate parameters.
Summary of Contents for SENTRON PAC5100
Page 8: ...8 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Page 10: ...10 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Page 264: ...264 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...