
8 Operation at Use of the Display
8.4 Parameterization
203
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
Table 8-3
Basic Parameter Settings
Parameter
Default Setting
Setting Range
Voltage Inputs
Connection type
The connection type is indicated on the display. However, it can be set via
the User interface only.
Rated value
The rated value is indicated on the display. However, it can be set via the
User interface only.
Use PTs?
No
(no checkmark)
Yes (checkmark)
No (no checkmark)
Use PTs:
V primary
Primary rated voltage Ph-Ph
AC 10,000.00 V
AC 100.00 V to 1,000,000.00 V
Use PTs:
V secondary
Secondary rated voltage Ph-
Ph
AC 100 V
AC 1.0 V to 1000.0 V
Current Inputs
Rated value
AC 5 A
AC 1 A
AC 5 A
Use CTs?
No
(no checkmark)
Yes (checkmark)
No (no checkmark)
Use CTs:
I primary
primary rated current
AC 1,000.00 A
AC 1.0 A to 100,000.0 A
Use CTs:
I secondary
secondary rated current
AC 1.00 A
AC 0.01 A to 10 A
Zero-Point Suppression
Zero-point suppression
(in % of Vrated
and Irated)
0.3 % 0.0 %
to
10.0 %
Summary of Contents for SENTRON PAC5100
Page 8: ...8 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Page 10: ...10 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...
Page 264: ...264 SENTRON PAC5100 5200 7KM5212 5412 Device Manual E50417 H1040 C568 A1 Edition 03 2015 ...