7 Operation at Use of a PC
7.3 Configuration of the Device
145
SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
7.3.5.5 Report Configuration
The
Report configuration
allows you to parameterize the PQ threshold parameters (
User defined
). You can
adjust the process connections to the installation environment and enter different operational settings.
Alternatively, you can use the default values according to
EN 50160 LV&MV
or
EN 50160 HV
.
Default Settings and Setting Ranges
1)
When an event has occurred, with this setting the recordings of the measurement recorder and trend re-
corder are marked in red on the
Find result
list (see Functioning of the Measuring System according to IEC
61000-4-30, 7.4.2.1 and 7.4.2.2).
2)
According to EN 50160, up to 3 % unbalance can occur in 3-wire networks in areas with many 1-wire and
2-wire connections.
Table 7-15
Report Configuration
Parameter
Default Setting
Setting Range
General Information
Company:
Department:
Supervisor:
Inspector:
Location:
Comment:
-
Any text displayed in the
printout of the power quality
report
Power Quality Report
Evaluation mode according to:
EN 50160 LV&MV
EN 50160 LV&MV
EN 50160 HV
User defined
Flagging acc. to
IEC 61000-4-30
no
no
yes
1)
Power frequency
99.5 % of measurand should be in -1.0 % to 1.0 % deviation of the power
frequency.
100 % of measurand should be in -6.0 % to 4.0 % deviation of the power
frequency.
Any setting for user-defined
evaluation mode
Power supply voltage magnitude
95 % of measurand should be in -10.0 % to 10.0 % deviation of the
declared input voltage Udin.
100 % of measurand should be in -15.0 % to 10.0 % deviation of the
declared input voltage Udin.
Any setting for user-defined
evaluation mode
Flicker severity
95 % of measurand should be less than 1.0
Voltage unbalance
2)
95 % of measurand should be less than 2.0 %.
100 % of measurand should be less than 3.0 %.
Any setting for user-defined
evaluation mode
Subgroup Total Harmonic Distortion factor (THDS)
95 % of measurand should be less than 8.0 %.
Any setting in % for user-
defined evaluation mode
Voltage event interruptions
1. Short interruption until 1 second duration
2. Short interruption until 3 minute duration
3. Long interruption longer than 3 minute duration
Any setting for user-defined
evaluation mode
Harmonic voltages
Even harmonics
Odd harmonics: multiples of 3
Odd harmonics: not multiples of 3
Any setting for user-defined
evaluation mode