Technical data
10.1 Technical data
96
PAC3120 and PAC3220
Equipment Manual, 10/2019,
L1V30425208F-01
Measuring inputs for voltage
Measuring inputs for voltage
Measurable voltage
Rated voltage
57.7/100 … 400/690 V (IEC)
57.7/100 … 347/600 V (UL)
Min. measuring voltage U
L-N
11.5 V
Max. measuring voltage U
L-N
480 V (IEC)
416 V (UL)
Zero point suppression level
Voltage L-N
10 V
Voltage L-L
17 V
Measuring category
(acc. to IEC/UL 61010-2-030)
Category
CAT III
Impulse withstand voltage
≥
9.6 kV (1.2/50
μ
s)
Input resistance (L N)
1.5 M
Ω
Max. power consumption per phase
150 mW
Measuring inputs for current
Only for connection to AC power systems via external current transformers.
Measuring inputs for current
Input current I
E
Rated current 1
x/1 A
Rated current 2
x/5 A
Measuring range of current
10 … 120 % of rated current
Measuring range for power and energy measurement
1 … 120 % of rated current
Surge withstand capability
100 A for 1 s
Max. permissible continuous current
10 A
Max. power consumption per phase
300 mVA at 5 A
Zero point suppression level
0 … 10 % of rated current
Summary of Contents for SENTRON PAC3120