Appendix
A.1 Modbus
PAC3120 and PAC3220
Equipment Manual, 10/2019,
L1V30425208F-01
137
Offset
Number of
registers
Name
Format
Value range
Access
63023
2
Data bits
Parity bits
Stop bits
1)
Unsigned
long
0 = 8N2
1 = 8E1
2 = 8O1
3 = 8N1
RW
63025
2
Response time
1)
Unsigned
long
0 … 255
RW
1)
Applies only to the PAC RS485 expansion module
2)
Applies only to the PAC3220
Addressing the settings for the I&M data
Table A- 12 Addressing the settings for the I&M data
Offset
Number of
registers
Name
Format
Applicable Modbus
function codes
Access
64001
27
I&M 0 data
stIM0
•
0x03
•
0x04
R(W)
64028
89
I&M 1 data … I&M 4 data
stIM14
•
0x03
•
0x04
•
0x10
RW
64117
27
I&M data module interface 1
1)
stIM0
•
0x03
•
0x04
R(W)
64144
27
I&M data module interface 2
1)
stIM0
•
0x03
•
0x04
R(W)
1)
Applies only to PAC3220