Commissioning
5.3 Parameterizing the device
PAC3120 and PAC3220
Equipment Manual, 10/2019,
L1V30425208F-01
57
5.3.1
Basic parameters
Set the basic parameters:
●
Connection type
●
Voltage
– Direct measurement on the system or using voltage transformers
– Measuring input voltage in the case of direct measurement on the system
– Primary and secondary voltage in the case of measurement using voltage
transformers
●
Current
– Primary current
– Secondary current
You can find additional information in chapters Operator control (Page 61) and Parameter
assignment (Page 69).
Example
You want to measure in a 3P4W 10 kV system using voltage transformers (10000 V/100 V)
and current transformers (100 A/5 A).
1. Select the "BASIC PARAMETERS" submenu of the "SETTINGS" menu.
Specify the connection type and the ratio of the voltage transformers you are using in the
"VOLTAGE INPUT" menu item.
The ratio of the voltage transformer used can be adjusted only when the setting USE
PTs? is activated.
2. Confirm your entry and press <ESC> to return to the "BASIC PARAMETERS" submenu.
Specify the ratio of the current transformers you are using in the "CURRENT INPUT"
menu item.
3. You can configure the resolution of the current display in the "DISPLAY RANGE" menu
item.
The setting has no impact on the measurement accuracy of the device.