Appendix
A.1 Modbus
PAC3120 and PAC3220
Equipment Manual, 10/2019,
L1V30425208F-01
125
Offset
Number of
registers
Name
Unit
Format
Value range
Access
50061 2
Display time until dimmed
min
Unsigned
long
0 … 99
RW
50063 2
Limit 0 ON/OFF
–
Unsigned
long
0 … 1
0 = Off
1 = On
RW
50065 2
Limit 0 Hysteresis
%
Float
0.0 … 20.0
RW
50067 2
Limit 0 Delay
s
Unsigned
long
0 … 10
RW
50069 2
Limit 0 Index (NO/AND/OR)
–
Unsigned
long
0 … 2
0 = NO
1 = AND
2 = OR
RW
50071 2
Limit 0 Index of data list
–
Unsigned
long
0 … 36
RW
50073 2
Limit 0 Source
–
Float
–
RW
50075 2
Limit 0 Type
≥
/<
–
Unsigned
long
0 … 1
0 = Greater than
1 = Smaller than
RW
50077 2
Limit 1 ON/OFF
–
Unsigned
long
0 … 1
0 = Off
1 = On
RW
50079 2
Limit 1 Hysteresis
%
Float
0.0 … 20.0
RW
50081 2
Limit 1 Delay
s
Unsigned
long
0 … 10
RW
50083 2
Limit 1 Index (NO/AND/OR)
–
Unsigned
long
0 … 2
0 = NO
1 = AND
2 = OR
RW
50085 2
Limit 1 Index of data list
–
Unsigned
long
0 … 36
RW
50087 2
Limit 1 Source
–
Float
–
RW
50089 2
Limit 1 Type
≥
/<
–
Unsigned
long
0 … 1
0 = Greater than
1 = Smaller than
RW
50091 2
Limit 2 ON/OFF
–
Unsigned
long
0 … 1
0 = Off
1 = On
RW
50093 2
Limit 2 Hysteresis
%
Float
0.0 … 20.0
RW
50095 2
Limit 2 Delay
s
Unsigned
long
0 … 10
RW
50097 2
Limit 2 Index (NO/AND/OR)
–
Unsigned
long
0 … 2
0 = NO
1 = AND
2 = OR
RW
50099 2
Limit 2 Index of data list
–
Unsigned
long
0 … 36
RW
50101 2
Limit 2 Source
–
Float
–
RW