Technical data
10.1 Technical data
102
PAC3120 and PAC3220
Equipment Manual, 10/2019,
L1V30425208F-01
Connection components: Communication ports PAC3120
Connection components: Communication ports PAC3120
Conductor cross-section for copper
cable (Cu)
Rigid
0.14 … 1.5 mm
2
(AWG 26 … 16)
Flexible
0.14 … 1.5 mm
2
(AWG 26 … 16)
Flexible with end sleeve, without plastic
sleeve
0.25 … 1 mm
2
(AWG 24 … 18)
Flexible with end sleeve and plastic
sleeve
0.25 … 1.5 mm
2
(AWG 24 … 16)
2 conductors (same cross-section)
Rigid
0.14 … 0.75 mm
2
(AWG 26 … 19)
Flexible
0.14 … 0.75 mm
2
(AWG 26 … 19)
Flexible with end sleeve, without plastic
sleeve
0.25 … 0.5 mm
2
(AWG 24 … 20)
Flexible with TWIN end sleeve and
plastic sleeve
0.5 … 1 mm
2
(AWG 20 … 18)
Tightening torque
0.5 ... 0.6 Nm
(4.4 … 5.3 lb-in)