
Technical data
10.1 Technical data
PAC3120 and PAC3220
Equipment Manual, 10/2019,
L1V30425208F-01
101
Connection components: Current connection, voltage connection
Connection components: Current connection, voltage connection
Conductor cross-section for copper
cable (Cu)
Rigid
0.2 … 6 mm
2
(AWG 24 … 10)
Flexible
0.2 … 4 mm
2
(AWG 24 … 12)
Flexible with end sleeve, without plastic
sleeve
0.2 … 4 mm
2
(AWG 24 … 12)
Flexible with end sleeve and plastic
sleeve
0.25 … 4 mm
2
(AWG 24 … 12)
2 conductors (same cross-section)
Rigid
0.2 … 1.5 mm
2
(AWG 24 … 16)
Flexible
0.2 … 1.5 mm
2
(AWG 24 … 16)
Flexible with end sleeve, without plastic
sleeve
0.25 … 0.75 mm
2
(AWG 24 … 19)
Flexible with TWIN end sleeve and
plastic sleeve
0.5 … 2.5 mm
2
(AWG 20 … 14)
Tightening torque
0.5 ... 0.6 Nm
(4.4 … 5.3 lb-in)
Summary of Contents for SENTRON PAC3120
Page 1: ...PAC3120 and PAC3220 ...
Page 2: ......
Page 8: ...Table of contents 6 PAC3120 and PAC3220 Equipment Manual 10 2019 L1V30425208F 01 ...
Page 110: ...Technical data 10 2 Labeling 108 PAC3120 and PAC3220 Equipment Manual 10 2019 L1V30425208F 01 ...
Page 159: ......
Page 160: ......