Appendix
A.1 Modbus
PAC3120 and PAC3220
Equipment Manual, 10/2019,
L1V30425208F-01
123
A.1.7
Modbus settings with the function codes 0x03, 0x04 and 0x10
Addressing the settings
You can use the Modbus function codes 0x03 and 0x04 for read access operations and 0x10
for write access operations on all the setting parameters listed below.
Table A- 10 Setting parameters
Offset
Number of
registers
Name
Unit
Format
Value range
Access
50001 2
Connection type
–
Unsigned
long
0 … 4
0 = 3P4W
1 = 3P3W
2 = 3P4WB
3 = 3P3WB
4 = 1P2W
RW
50003 2
Voltage measurement using voltage
transformer yes/no
–
Unsigned
long
0 … 1
0 = No
1 = Yes
RW
50005 2
Primary voltage
V
Unsigned
long
1 … 999999
RW
50007 2
Secondary voltage
V
Unsigned
long
1 … 480
RW
50011 2
Primary current
A
Unsigned
long
1 … 99999
RW
50013 2
Secondary current
A
Unsigned
long
1 … 5
RW
50019 2
Zero point suppression level
%
Float
0.0 … 10.0
RW
50021 2
Demand period
Min.
Unsigned
long
1 … 60
RW
50023 2
Synchronization
–
Unsigned
long
0 … 2
0 = No synchronization
1 = Synchronization via bus
2 = Synchronization via digi-
tal input
RW
50025 2
DI 0.0 Type of use
–
Unsigned
long
0 … 3
0 = No action
1 = Pulse interface
2 = Switching on/off peak
3 = Synchronization
RW
50029 2
DI 0.0 Index
–
Unsigned
long
0 … 1
0 = kWh
1 = kvarh
RW
50031 2
DI 0.0 Pulses per unit
–
Unsigned
long
1 … 4000
RW
50033 2
DO 0.0 Vector group assignment
–
Unsigned
long
0 … 99
RW