Parameter assignment
7.2 Parameterizing via the operator interface
PAC3120 and PAC3220
Equipment Manual, 10/2019,
L1V30425208F-01
77
Digital input
Selection
Range
Factory setting
DIG. INPUT
Two digital inputs are available:
•
0.0
•
0.1
–
ACTION
•
NONE:
The input is switched off.
•
PULSE INPUT:
Counting of input pulses.
(Note: A universal counter can be parameter-
ized for pulse counting. In the device settings
"ADVANCED > UNIVERSAL COUNTER", set
the field "SOURCE" to the value
"DIG. INPUT".)
•
ON/OFF-PEAK:
Tariff switching.
Low tariff if input active.
•
DEMAND SYNC:
Synchronization of power demand.
•
LIM.VIOLATION:
The output is switched on by a limit violation
and remains active while the limit violation
prevails.
•
PULSE:
Output outputs the parameterized number of
pulses or edges per energy unit.
OFF
PULSES
Number of pulses to be output per unit. The ref-
erence unit is defined in the "UNIT" field.
1 … 4000
1