Appendix
A.1 Modbus
132
PAC3120 and PAC3220
Equipment Manual, 10/2019,
L1V30425208F-01
Offset
Number of
registers
Name
Unit
Format
Value range
Access
51724 1
DO 0.1 Index
–
Unsigned
short
0 … 3
0 = Import kWh
1 = Export kWh
2 = Import kvarh
3 = Export kvarh
RW
51725 1
DO 0.1 Pulses per kWh/kvarh
–
Unsigned
short
1 … 4000
RW
51726 1
DO 0.1 Pulse length
–
Unsigned
short
30 … 500
RW
51727 1
DO 0.1 Timeout
–
Unsigned
short
0.1 … 18000
Digital output remote timeout
1 … 18000 s, 0 = Disables
timeout (default)
RW
51728 1
DO 0.1 Pulse divider
–
Unsigned
short
0 … 3
0 = 1 kWh
1 = 10 kWh
2 = 100 kWh
3 = 1000 kWh
RW
51729 1
DO 4.0 Group assignment
–
Unsigned
short
0 … 99
RW
51730 1
DO 4.0 Type of use
–
Unsigned
short
0 … 5
0 = No action
1 = Device active
2 = Switching output
3 = Direct. of rotation
4 = Limit value
5 = Pulse output
RW
51731 1
DO 4.0 Limit value index
–
Unsigned
short
0 … 6
0 = Comb. limit
1 = Limit0
2 = Limit1
3 = Limit2
4 = Limit3
5 = Limit4
6 = Limit5
RW
51733 1
DO 4.0 Index
–
Unsigned
short
0 … 3
0 = Import kWh
1 = Export kWh
2 = Import kvarh
3 = Export kvarh
RW
51734 1
DO 4.0 Pulses per kWh/kvarh
–
Unsigned
short
1 … 4000
RW
51735 1
DO 4.0 Pulse length
–
Unsigned
short
30 … 500
RW
51736 1
DO 4.0 Timeout
–
Unsigned
short
0.1 … 18000
Digital output remote timeout
1 … 18000 s, 0 = Disables
timeout (default)
RW
Summary of Contents for SENTRON PAC3120
Page 1: ...PAC3120 and PAC3220 ...
Page 2: ......
Page 8: ...Table of contents 6 PAC3120 and PAC3220 Equipment Manual 10 2019 L1V30425208F 01 ...
Page 110: ...Technical data 10 2 Labeling 108 PAC3120 and PAC3220 Equipment Manual 10 2019 L1V30425208F 01 ...
Page 159: ......
Page 160: ......