Parameter assignment
7.2 Parameterizing via the operator interface
PAC3120 and PAC3220
Equipment Manual, 10/2019,
L1V30425208F-01
75
7.2.5
Integrated I/Os
Device settings for using the digital inputs and outputs.
Digital output
Selection
Range
Factory setting
DIG. OUTPUT
Two digital outputs are available:
•
0.0
•
0.1
–
ACTION
•
OFF:
Output is deactivated.
•
DEVICE ON:
Output signals that the device is switched on.
•
REMOTE CONTROL:
Output is controlled by remote access.
•
DIRECTION OF ROTATION:
Output is activated by a clockwise rotating
electrical field and remains active for as long
as the field is rotating in this direction.
•
PULSE: Output outputs the parameterized
number of pulses or edges per energy unit.
OFF
PULSES
Number of pulses to be output per unit. The ref-
erence unit is defined in the "UNIT" field.
1 … 4000
1
UNIT
(with PULSE only)
Selects the type of cumulated power (active en-
ergy or reactive energy):
•
kWh IMPORT
•
kWh EXPORT
•
kvarh IMPORT
•
kvarh EXPORT
The reference values at which a pulse or an edge
is output are defined in the fields "UNIT" and
"PULSES PER UNIT".
Value of the cumulated power for which a config-
urable number of pulses is output. The number of
pulses to be output is defined in the field "PER".
•
1 kVarh or kW
•
10 kVarh or kW
•
100 kVarh or kW
•
1000 kVarh or kW
kWh IMPORT