Appendix
A.1 Modbus
PAC3120 and PAC3220
Equipment Manual, 10/2019,
L1V30425208F-01
143
File
(FC0x14)
Offset
Address
Address
FC 0x03
FC 0x04
Length
Name
Format
Access
1
579
30579
2
min_VA_SUM
Float
R
1
581
30581
2
min_P_SUM
Float
R
1
583
30583
2
min_VARQ1_SUM
Float
R
1
585
30585
2
min_PF_SUM
Float
R
1
587
30587
2
min_V_BAL
Float
R
1
589
30589
2
min_I_BAL
Float
R
1
591
30591
2
min_I_N
Float
R
2
1
31001
2
Time stamp aggregation stage n
UNIX_TS
R
2
3
31003
2
Flags aggregation stage n
Uint32
R
2
5
31005
2
V_L1
Float
R
2
7
31007
2
V_L2
Float
R
2
9
31009
2
V_L3
Float
R
2
11
31011
2
V_L12
Float
R
2
13
31013
2
V_L23
Float
R
2
15
31015
2
V_L31
Float
R
2
17
31017
2
I_L1
Float
R
2
19
31019
2
I_L2
Float
R
2
21
31021
2
I_L3
Float
R
2
23
31023
2
VA_L1
Float
R
2
25
31025
2
VA_L2
Float
R
2
27
31027
2
VA_L3
Float
R
2
29
31029
2
P_L1
Float
R
2
31
31031
2
P_L2
Float
R
2
33
31033
2
P_L3
Float
R
2
35
31035
2
VARQ1_L1
Float
R
2
37
31037
2
VARQ1_L2
Float
R
2
39
31039
2
VARQ1_L3
Float
R
2
41
31041
2
PF_L1
Float
R
2
43
31043
2
PF_L2
Float
R
2
45
31045
2
PF_L3
Float
R
2
47
31047
2
THDV_L1
Float
R
2
49
31049
2
THDV_L2
Float
R
2
51
31051
2
THDV_L3
Float
R
2
53
31053
2
THDI_L1
Float
R
2
55
31055
2
THDI_L2
Float
R
2
57
31057
2
THDI_L3
Float
R
2
59
31059
2
FREQ
Float
R
2
61
31061
2
V_LN_AVG
Float
R
2
63
31063
2
V_LL_AVG
Float
R
2
65
31065
2
I_AVG
Float
R
Summary of Contents for SENTRON PAC3120
Page 1: ...PAC3120 and PAC3220 ...
Page 2: ......
Page 8: ...Table of contents 6 PAC3120 and PAC3220 Equipment Manual 10 2019 L1V30425208F 01 ...
Page 110: ...Technical data 10 2 Labeling 108 PAC3120 and PAC3220 Equipment Manual 10 2019 L1V30425208F 01 ...
Page 159: ......
Page 160: ......