Appendix
A.1 Modbus
138
PAC3120 and PAC3220
Equipment Manual, 10/2019,
L1V30425208F-01
A.1.9
Modbus command parameters
Addressing the command parameters
You can use Modbus function code 0x06 on the command parameters.
Table A- 13 Command parameters
Offset
Number of
registers
Name
Unit
Format
Value range
Access
60000 1
Reset the device to the factory set-
tings
–
Unsigned
short
–
W
60001 1
Device reset (without changing the
Modbus address)
–
Unsigned
short
–
W
60002 1
Reset maximum values
–
Unsigned
short
0
W
60003 1
Reset minimum values
–
Unsigned
short
0
W
60004 1
Reset energy counters
–
Unsigned
short
0 =
all
W
1 =
Active energy
import tariff 1
2 =
Active energy
import tariff 2
3 =
Active energy
export tariff 1
4 =
Active energy
export tariff 2
5 =
Reactive energy
import tariff 1
6 =
Reactive energy
import tariff 2
7 =
Reactive energy
export tariff 1
8 =
Reactive energy
export tariff 2
9 =
Apparent ener-
gy tariff 1
10 =
Apparent ener-
gy tariff 2
60005 1
Synchronization of the demand
period
min
Unsigned
short
1 … 60
W
60006 1
Tariff switchover
–
Unsigned
short
0 = On-peak
1 = Off-peak
W
60007 1
Acknowledge the diagnostics bits
1)
(cf. stored bits in unsigned long
beginning offset 205)
–
Unsigned
short
0 … ffffh
W
60008 1
Switch outputs (if parameterized)
–
Unsigned
short
0ffh … 1ffh
W
Byte0 0 = Output 0.0