NOTICE
Do not cover the ventilation grilles
During installation, select a mounting position so that the ventilation grilles are always free to
achieve adequate cooling. With normal orientation, the ventilation grilles are on the top,
bottom and sides (SCALANCE X204RNA EEC only) of the housing.
Minimum clearances
If you install the SCALANCE X-200RNA without forced ventilation or cooling, minimum
clearances must be maintained to neighboring devices or the wall of the housing. By keeping
to the minimum clearances, there is then an adequate stream of air for heat dissipation during
operation. Keep to the following minimum clearances to neighboring devices.
Table 5-1
Minimum clearances when installing in cabinets
Minimum clearance to devices below the SCALANCE X-200RNA
100 mm
Minimum clearance to devices above the SCALANCE X-200RNA
100 mm
Minimum lateral clearance to devices (SCALANCE X204RNA EEC only) 20 mm
Installation
5.1 Types of installation
SCALANCE X-200RNA
56
Operating Instructions, 10/2016, C79000-G8976-C342-04