![Siemens SCALANCE X-200RNA Operating Instructions Manual Download Page 30](http://html.mh-extra.com/html/siemens/scalance-x-200rna/scalance-x-200rna_operating-instructions-manual_383816030.webp)
Note
PROFINET controllers can communicate with PROFINET devices via the HSR and PRP
network (PROFINET IO and RT). In this case all PROFINET devices (controllers and devices)
must either be capable of HSR or PRP themselves or must be connected to the HSR ring or
to the PRP network via a RedBox.
Within a PRP network (A or B), PROFINET controllers and devices can also communicate with
each other as SANs (PROFINET IO, RT and IRT). A direct PROFINET communication
relationship between DANPs and SANs or DANHs and SANs is not supported.
Table 4-2
Overview of the connection options
Fast Ethernet 100 Mbps
SCALANCE X204RNA
SCALANCE X204RNA EEC
TP (RJ‑45)
4
2+2
Fiber
multimode
(duplex LC)
-
2 x SFP modules SFP991-1
multimode glass up to 3 km
6GK5991-1AD00-8AA0
Fiber
single mode
(duplex LC)
-
2 x SFP modules SFP991-1LD
monomode glass up to 26 km
6GK5991-1AF00-8AA0
Fiber
single mode
(duplex LC)
-
2 x SFP modules SFP991-1LH+
monomode glass up to 70 km
6GK5991-1AE00-8AA0
Standard Ethernet ports / PRP ports
P1/A, P2/B
P1/A, P2/B
HSR ports
HSR 1, HSR 2
HSR 1, HSR 2
Note
TP connectors of SCALANCE X204RNA EEC
The SCALANCE X204RNA EEC has 2 RJ-45 ports to which you can connect two standard
Ethernet or PRP end devices/network structures without HSR capability.
The SCALANCE X204RNA EEC also has 2 RJ-45 ports and 2 SFP slots. These connection
options communicate with each other; in other words only one connector is ever active. If an
SFP module is inserted, the corresponding RJ-45 jack is disabled.
With these connector options, you can connect the device to an HSR ring.
Descriptions of the products
4.1 Overview of the product characteristics
SCALANCE X-200RNA
30
Operating Instructions, 10/2016, C79000-G8976-C342-04
Summary of Contents for SCALANCE X-200RNA
Page 6: ...Table of contents SCALANCE X 200RNA 6 Operating Instructions 10 2016 C79000 G8976 C342 04 ...
Page 12: ...Introduction SCALANCE X 200RNA 12 Operating Instructions 10 2016 C79000 G8976 C342 04 ...
Page 16: ...Safety notices SCALANCE X 200RNA 16 Operating Instructions 10 2016 C79000 G8976 C342 04 ...