Siemens
Central control unit RMB795B
CE1P3122en
Building Technologies
Function block: "faults"
18.01.2012
No.
Standard text
Effect
9004
[Fault inp 4] fault
Ditto
9005
[Fault inp 5] fault
Ditto
9006
[Fault inp 6] fault
Ditto
9007
[Fault inp 7] fault
Ditto
9008
[Fault inp 8] fault
Ditto
9009
[Fault inp 9] fault
Ditto
9010
[Fault inp 10] fault
Ditto
The fault with the highest priority is sent over the KNX bus. If more than one fault
input wants to report priority "Urgent", the message ">1 fault input faulty" is sent at
the highest priority. Only the message from one fault input would otherwise be
known within this fault message. The newly arriving fault message can be viewed
on the Info level under "Fault status message bus".
10.4 External fault button
The fault block allows for connecting an external fault button. The external fault
button has the same function as fault button " " on the RMB795B. Both can be
operated in parallel. The current alarm state can be externally indicated via the
fault relay.
N.X1
N.X2
N.X3
N.X4
N.X5
N.X6
N.X7
N.X8
Faults
Main menu > Commissioning > Extra configuration > Faults >
Operating line
Adjustable values / remarks
Fault button external
---, N.X1, N.X2, ...
(digital only).
10.5 Fault relay
To pass on fault status messages, or to have them optically or acoustically
indicated on a control panel, for example, 2 fault status outputs "Relay1" and
"Relay2" of the function block can be configured to any 2 free outputs N.Qx of the
central control unit RMB795B.
>1 fault input faulty
Configuration
Route fault status
messages