Passing on the setpoints from the RMB795B central control unit to the RXB/RXL
room controllers takes place only if, during room group configuration, "Setpoint
priority" has been set to "Yes".
Additional setpoint readjustments can be made on the RXB/RXL room controller by
means of the QAX room unit or the OCI700.1 service tool. These settings are not
shown in the examples.
8.5
Temperatures "Reference rooms"
1 to 3 specially selected individual rooms can be defined as reference rooms,
which are used for calculating the "Night cooling" function.
The temperatures of the reference rooms can be displayed for each room group.
The reference rooms can be defined in the
Communication
menu:
Commissioning > Communication > Room group x > Reference room x
See Sec. 13.2.2 "Room group 1...10".
The temperature values for the reference rooms are displayed under the menu
item
Room temp actual value
:
Main menu > Room group 1…10 > Room temp actual value
Operating line
Actual room temperature
Reference room 1
Temperature value for reference room 1.
Reference room 2
Temperature value for reference room 2.
Reference room 3
Temperature value for reference room 3.
"Reference room X" is the default text. It can be edited and will then be displayed.
8.6
Temperature supervision
Temperature supervision should provide an overview of the temperature
distribution in a room group. For this purpose, the following temperatures are
displayed:
•
The highest current room temperature in a room group and the zone address of
the relevant RXB/RXL room controller
•
The lowest current room temperature in a room group and the zone address of
the relevant RXB/RXL room controller
The evaluation is made in the form of a dynamic list which constantly records the
highest and the lowest valid room temperature.
A device must be created as described in Sec. 16.3 "Create device list" for
temperature supervision to work.
Main menu > Room group 1…10 > Room temp actual value >
Operating line
Description
Highest room
temperature
Currently highest room temperature in a room group
Zone (Apart.Room)
Geographical zone address of the RXB/RXL room
controller with the highest room temperature, e.g. 2.1.
Lowest room
Currently lowest room temperature in a room group.
Notes
Purpose
Configuration
Display values
Note
Purpose
Note
Display values