67 / 144
Siemens
Central control unit RMB795B
CE1P3122en
Building Technologies
Function block: "Room group"
18.01.2012
When handling errors, a differentiation is made between the 2 following cases:
Only one master may be set per holiday / special day zone (see Sec. 13.2.2 "Room
group 1…10).
If several devices are set as masters, a fault status message occurs. The device,
that receives two holiday/special day signals, sends the message.
If the RMB795B central control unit expects a holidays/special day signal from the
bus and it is not communicated, the following fault status message is sent:
"Hol/spec day program failure".
In both cases, the operating modes of the 7-day program are used, without giving
consideration to the holiday / special day entries.
No.
Text
Effect
5201
Hol/spec day prog room group
1
Non urgent message; must not be
acknowledged.
... ...
...
5291
Hol/spec day prog room group
10
Ditto
5202
>1 hol/spec day prog R’grp. 1
Non-urgent message; must be
acknowledged.
... ...
...
5292
>1 hol/spec day prog R’grp. 10 Ditto
When evaluating the priority in the holidays / special day program, only the first 2
entries are taken into consideration. If more than two overlapping entries are made,
the special day may no longer have priority over the holidays.
8.3.7
Room operating mode outputs
Outputs Relays 1 / 2" (operating mode relays) at the function block make it
possible to feed the resulting room operating mode of the respective room group to
2 relays Qx of the RMB795B central control unit.
Forwarding the resulting room operating mode from the Qx relay outputs of the
central control unit to a Synco™200 controller:
G
G0
AC
2
4 V
G
G0
M D1
N2
31
21
A
05
G
G0
N1
Qx3
Qx4
Qx3
Qx4
M D2
N1: RMB795B
N2:
Synco™200 RLU2...
Troubleshooting
Fault status messages
Priorities
Purpose
Possible application
Key