Function block: "Room group"
18.01.2012
8.4.3
Summer/winter compensation
For each room group, summer / winter compensation can be parameterized. It is
active when the outside temperature is available. This function always acts
independently of setting parameter "Setpoint priority".
Summer / winter compensation shifts the setpoint of the RXB/RXL room controllers
according to the outside temperature.
The setpoint shift adjustment on the Comfort and Precomfort setpoints according to
the following diagram:
SpC
SpC
SpC
SpH
SpH
SpH
t
w
Δ
w
[K]
E
S
F
S
E
W
F
W
Δ
S
Δ
W
31
21
D
06
de
TA
Key:
F
S
Summer
compensation start
E
S
Summer compensation end
E
W
Winter compensation end
F
W
Winter compensation start
w
S
Summer compensation delta
w
W
Winter compensation delta
Summer/winter compensation is used for the following reasons:
•
Summer compensation to compensate for the lighter clothing worn by building
occupants
•
Winter compensation to give consideration to the cold envelope of the space
(e.g. the windows)
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Room group 1....10 > Setpoint effects >
Operating line
Range
Factory setting
Summer
compensation delta
0...
+
50.0 K
0 K
Summer
compensation end
Summer compensation
start…250 °C.
30 °C
Summer comp.
starting point
Winter compensation start
Summer compensation end
20 °C
Winter compensation
start
Winter compensation end
Summer comp. starting point
0 °C
Winter compensation
end
−
50.0…Winter compensation
start
−
10 °C
Winter compensation
delta
−
50.0...
+
50.0 K
0 K
If there is no outside temperature sensor signal, the controller does not adjust the
setpoint.
Activation
Operating principle
Application
Setting values