100 / 144
Siemens
Central control unit RMB795B
CE1P3122en
Building Technologies
Distribution zones
18.01.2012
11.3.3 Heat demand modulating
In addition to the heat demand relay, the heat demand can be made available at a
modulating output N.Yx for other devices.
Main menu > Commissioning > Extra configuration > Heat demand
Operating line
Adjustable values / remarks
Heat demand
modulating
---, N.Y1, N.Y2, ...
Activate output.
Main menu > Settings > Heat demand >
Operating line
Range
Factory setting
Setpoint at 0 V
–50…+50 °C
0 °C
Setpoint at 10 V
50…500 °C
100 °C
Limit value
–50…+250 °C
10 °C
"Setpoint at 0 V" determines the flow temperature setpoint at DC 0 V.
"Setpoint at 10 V" determines the flow temperature setpoint at DC 10 V.
"Limit value" denotes "Limit value for heat demand": Temperatures below this level
are interpreted as "no heat demand".
As long as the flow temperature setpoint does not exceed the set limit value, the
output signal DC 0 V is sent. When the limit value is exceeded, the relevant output
signal is sent until the setpoint is again below the limit value minus a hysteresis of
0.5 K.
Output signal Y (DC 0…10 V) for the heat demand corresponds to a flow
temperature setpoint range w
TV
of 0…120 °C. This limit value should be at 10 °C.
The diagram shows the values of the parameters to be set and the resulting
progression of the heat demand signal:
100
0
10
Y
[ V ]
[°C]
31
21
D
02
20
40
60
80
120
0
−
20
2
1
3
w
TV
1 Setpoint in °C at DC 0 V.
here 0 °C (factory setting)
2 Setpoint in °C at DC 10 V.
here 120 °C
3 Limit value for heat demand
here 10 °C (factory setting)
Purpose
Configuration
Setting values
Explanations relating to
the setting values
Diagram relating to the
setting values (example)
Key