Central control unit RMB795B
CE1P3122en
Building Technologies
General settings
18.01.2012
System should always be run in synchronized mode, that is, in master-slave
operation (1 master, all others as slaves).
6.1.3
Troubleshooting
In connection with the time of day and date, the RMB795B central control unit
generates a fault status message in the following cases:
•
If the clock on the bus is missing and the local clock is parameterized as the
clock time slave, operation continues with the internal clock and fault status
message "System time failure" will be delivered
•
If several devices on the bus are parameterized as clock time masters, fault
status message ">1 clock time master" will be delivered.
•
The clock in the central control unit has a reserve of 12 hours. If a power failure
exceeds 12 hours, the time of day must be readjusted.
If, after a power failure, the central control unit loses its time of day and it does
not receive it again via bus, fault status message "Invalid time of day" will be
delivered.
Note:
An invalid time of day flashes.
No.
Text
Effect
5001 System
time
failure
Non urgent message; must not be acknowledged.
5002 > 1 clock time
master
Non-urgent message; must be acknowledged.
5003 Invalid time of day Non urgent message; must not be acknowledged.
6.2
Select language
Every RMB795B central control unit has several languages loaded.
When switching on the central control unit for the first time, the
Language
menu
appears in English, independent of the unit’s language set. Select the required
language from that menu.
The language can also be changed later during operation. See data sheet N3132.
The following languages are loaded, depending on the type of central control unit:
Type
Language 1
Language 2 Language 3
Language 4 Language 5
Language 6
RMB795B-1 German
French
Italian
Spanish
Portuguese
-
RMB795B-2 German
French
Dutch
English
-
-
RMB795B-3 Danish
Finnish
Norwegian Swedish
-
-
RMB795B-4 Czech
Hungarian Polish
Slovakian Russian
Bulgarian
RMB795B-5 Romanian Slovenian Serbian
Croatian
Greek
Turkish
RMB795B-6 Chinese
-
-
-
-
-
Main menu > Commissioning > Settings >
…
or
Main menu > Settings > Device >
Operating line
Range
Factory setting
Language
English
Recommendation
Possible cases
Fault status messages
Behavior when
switching on for
the first time
Selection of languages
Setting values