Function block: "Room group"
18.01.2012
8.10.1 Activate function
The function is activated by configuring a digital input:
Main menu > Commissioning > Extra configuration > Room group 1…10 > Fire and smoke
extraction >
Operating line
Adjustable values / remarks
Fire alarm off
---, X1, X2, ... (digital inputs only).
8.10.2 Operating principle
When individual room controllers are used on applications that support the
"Emergency override" function, the RMB795B central control unit can transmit to
them via bus the signal for fire alarm off received via the digital input.
The signal acts on the geographical zone of the relevant room group. It has no
impact on the operating mode of that room group.
For detailed information about the RXB/RXL room controllers that support the
"Emergency override" function, refer to the relevant RXB/RXL documentation.
The signal at digital input X4 is forwarded to the inputs "Fire alarm off" of two room
groups:
x x
x
x
x
Q Q
x
x
x
1
2
Raumgruppe 2
x x
x
x
x
Q Q
x
x
x
1
2
N.X1
x Y
SI
G
N
AL
Y
N.X2
x Y
SI
G
N
AL
Y
N.X3
x Y
SI
G
N
AL
Y
N.X4
x Y
SI
G
N
AL
Y
N.X5
x Y
SI
G
N
AL
Y
N.X6
x Y
SI
G
N
AL
Y
Digital
31
21
Z
02e
n
SA EA
SA EA
Relay
Setpoint prio
Relay
Setpoint prio
Enable
Enable
8.10.3 Troubleshooting
Fault priority is always "urgent". A fire alarm signal must always be acknowledged
and reset. Only then will the room group(s) resume normal operation according to
the time program.
No.
Text
Effect
3890-
3899
Fire alarm off
Urgent message; must be acknowledged and
reset.
Configuration
Bus telegram to the
individual room
controllers
Note
Application example
Priority is urgent
Fault status messages