Siemens
Central control unit RMB795B
CE1P3122en
Building Technologies
Communication
18.01.2012
In RMS705B, device 2 (rooftop fan), the following is configured:
Main menu > Commissioning > Extra configuration > Input identifier >
Operating line
Range
Factory setting
N.X1 Digital
Main menu > Commissioning > Communication > LTE transmission zones >
Operating line
Range
Factory setting
N.Q1 2
Main menu > Commissioning > Communication > LTE reception zones >
Operating line
Range
Factory setting
N.X1 1
C
Zone 2
Zone 1
Logic 1
Unit 1
Unit 2
In the event an input is to receive as signal from the bus and this signal is
unavailable, the fault message "[...X...] sensor error" is sent after a period expires
(ca. 30 minutes).
No.
Text
Effect
5902
>1 identical LTE zone
Non urgent message; must not be
acknowledged.
Device 2
Configuration diagram
Fault status messages