Central control unit RMB795B
CE1P3122en
Building Technologies
General settings
18.01.2012
6.3
Select temperature unit
On the RMB795B, the unit of temperature can be switched between °C/K and °F.
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Device >
Operating line
Range
Factory setting
Unit
Degrees Celsius,
degrees Fahrenheit
°C
6.4
Operator unit display contrast
The contrast of the display can be matched to the environment.
Main menu > Commissioning > Settings >
…
or
Main menu > Settings > Device >
Operating line
Range
Factory setting
Contrast
0...100 %
50 %
6.5
Text entry
6.5.1
Device name
The text for the device name appears on the welcome screen:
Main menu > Commissioning > Settings >
…
or
Main menu > Settings > Texts >
Operating line
Range
Factory setting
device name
Max. 20 characters.
6.5.2
File name
The file name can be assigned individual text for the selected application:
Main menu > Commissioning > Settings >
…
or
Main menu > Settings > Texts >
Operating line
Range
Factory setting
File name
Max. 20 characters.
B
6.5.3
Electronic business card
The text for the electronic business card is displayed as an info picture. The
electronic visitor’s card must specially be activated in the extra configuration.
Main menu > Commissioning > Extra configuration > Miscellaneous > Business card
Operating line
Range
Factory setting
Business card
Yes, no
Yes
Setting values
Setting values
Setting values
Setting values
Configuration