![Siemens RMB795B Basic Documentation Download Page 51](http://html.mh-extra.com/html/siemens/rmb795b/rmb795b_basic-documentation_377324051.webp)
51 / 144
Siemens
Central control unit RMB795B
CE1P3122en
Building Technologies
Inputs
18.01.2012
7.4
Pulse
An input with this identifier can be used to connect a pulse counter. Pulses with the
following specification can be received:
•
Mechanical sources (Reed contact) without Namur circuitry, max. pulse
frequency of 25 Hz and a min. pulse duration of 20 ms.
•
Electronic pulse source with max. pulse frequency of 100 Hz and min. pulse
duration of 5 ms.
7.4.1
Activate function
Main menu > Commissioning > Extra configuration > Input identifier >
Operating line
Adjustable values / remarks
…X… Pulse
Electronic pulse sources (e.g. Open Collector outputs) generate shorter, less
bouncing pulses than mechanical pulse sources (e.g. relays or Reed contacts).
The type can be selected.
Main menu > Commissioning > Settings > ....
or
Main menu > Settings > Inputs > ...X...
Operating line
Range
Factory setting
Type
Mechanically or electronically
Mechanically
7.4.2
Connection diagram
G
G
G0
X...
M
G0
R1
N
31
23
A
10
A
C
24 V
+/-
+/-
R1
Reed pulse source.
Configuration
Setting value