Function block: "Room group"
18.01.2012
The
Outputs
menu shows the state of the operating mode relays:
Main menu > Room group 1…10 > Room operating mode >
Operating line
Current state
Operating mode relay
1
Off, On
Operating mode relay
2
Off, On
8.3.8
Functional check / wiring test
During the wiring test, the room operating mode outputs of the room groups can be
switched directly, enabling their function to be checked.
Main menu > Commissioning > Wiring test > Outputs
Operating line
Comments
Operating mode room
group 1…10
----, Comfort, Precomfort, Economy, Protection.
8.4
Setpoints and setpoint adjustments
8.4.1
Setpoints
Specific setpoints can be predefined for operating modes Comfort, Precomfort
and Economy for each room group.
The RXB/RXL room controllers adopt the setpoints only if configuration parameter
"
Setpoint priority
" has been set to "Yes". In that case, the setpoints locally
adjusted on the RXB/RXL room controller are overwritten by the setpoints of the
room group.
Main menu > Commissioning > Extra configuration > Room group 1…10 >
Operating line
Adjustable values / remarks
Setpoint priority
Yes, no
Main menu > Commissioning > Settings > …
or
Main menu > Settings > Room group 1...10 > Room temp. setpoint >
Operating line
Range
Factory setting
Economy cooling
setpoint
Precomfort cooling setpoint
… 250 °C
30 °C
Precomfort cooling
setpoint
Comfort cooling setpoint …
economy cooling setpoint
28 °C
Comfort cooling
setpoint
Comfort heating setpoint …
Precomfort cooling setpoint
24 °C
Comfort heating
setpoint
Precomfort heating setpoint
… Comfort cooling setpoint
21 °C
Precomfort heating
setpoint
Economy heating setpoint …
comfort heating setpoint
19 °C
Economy heating
setpoint
–50.0 °C... Precomfort
heating setpoint
15 °C
Display values
Purpose
Setting values
Preselected setpoints
per room group
Configuration
Setting values