6AW5451-6XX01-1K
ES 030-K Manual
5 - 6
Subject to change without prior notice
RD: 08.2000
(4)J31069-D0136-U001-A0-7618
5.3.7
Serial Interface TTY/V.24
6AW5458-7BB
Channel 1
data reception line is jumpered for CTS
(pin 3 - pin 5)
V.24
open
BR2
BR1
BR3
BR5
BR4
BR 1
BR 3
normal operation
BR 4
TTY
BR 5
jumpered for RTS - CTS (pin 4 - pin 5)
BR2
Caution:
CTS is not designed for dynamic opera
tion (output stop on precise bit).
When CTS = 0, data output is stopped
on ES 030-K.
When CTS = 1, interface of the
ES 030-K is processed again.
In addition, the data communication of
two partners can be coordinated with
the XON/XOFF software handshake
when the LAUF procedure is used.
XON = 11H = ready
XOFF = 13H = busy
Control of data output:
Use of a V.24 interface on connector X2. X3 with serial
expansion module: ES 030-K only evaluates the CTS
control line.
5.3.8
PROFIBUS-DP
6AW5458-7AE
X1
X2
H8
H7
H6
H1 H2
CPU
EPROM
SPC
This module does not require jumper adjustments. Para
meterisation is performed by the software.
Meaning of the LEDs:
LED H6: RED = PROFIBUS-DP interface
TxD (sending data)
LED H7: RED = PROFIBUS-DP interface
RTS (request to send)
LED H8: RED = PROFIBUS-DP interface
RxD (receiving data)
On
Off
Flashing
On
Off
Off
LED
H1
H2
Off
Off
Off
On
Flashing
On
LED H1: RED =
Bus error by PROFIBUS-DP
LED H2: GREEN = PROFIBUS-DP is running.
Profibus-DP not initialized
- Master does not address
ES 030-K. DB1/DL88 contains
the wrong bus address
- Wrong parameterisation of the
ES 030-K on bus master
- Bus cable not connected to the
ES 030-K or is defective
Initialization running
Error during initialization
PROFIBUS-DP timeout
Error in configuration of master
PROFIBUS-DP is okay and running.