Issue 04/02
Safety Instructions
MICROMASTER 410 Operating Instructions
6SE6400-5EA00-0BP0
9
Operation
WARNING
♦
MICROMASTERS operate at high voltages.
♦
When operating electrical devices, it is impossible to avoid applying
hazardous voltages to certain parts of the equipment.
♦
Emergency Stop facilities according to EN 60204 IEC 204 (VDE 0113) must
remain operative in all operating modes of the control equipment. Any
disengagement of the Emergency Stop facility must not lead to uncontrolled
or undefined restart.
♦
Wherever faults occurring in the control equipment can lead to substantial
material damage or even grievous bodily injury (i.e. potentially dangerous
faults), additional external precautions must be taken or facilities provided to
ensure or enforce safe operation, even when a fault occurs (e.g. independent
limit switches, mechanical interlocks, etc.).
♦
Certain parameter settings may cause the inverter to restart automatically
after an input power failure.
♦
Motor parameters must be accurately configured for motor overload
protection to operate correctly.
♦
This equipment is capable of providing internal motor overload protection in
accordance with UL508C section 42. Refer to P0610 and P0335, I
2
t is ON by
default.
♦
This equipment is suitable for use in a circuit capable of delivering not more
than 10,000 symmetrical amperes (rms), for a maximum voltage of
115 V/230 V, when protected by a H or K type fuse.
♦
This equipment must not be used as an ‘emergency stop mechanism’
(see
EN 60204, 9.2.5.4)
Repair
WARNING
♦
Repairs on equipment may only be carried out by
Siemens Service
, by
repair centers
authorized by Siemens
or by qualified personnel who are
thoroughly acquainted with all the warnings and operating procedures
contained in this manual.
♦
♦
♦
♦
Any defective parts or components must be replaced using genuine Siemens
authorised parts.
♦
Risk of electric shock.
Wait 5 minutes for the DC capacitors to discharge
before carrying out any installation work.
Dismantling & Disposal
NOTES
♦
The inverter’s packaging is re-usable. Retain the packaging for future use or
return it to the manufacturer.
♦
Easy-to-release screw and snap connectors allow you to break the unit down
into its component parts. You can then re-cycle these component parts,
dispose of them in
accordance with local requirements or return them to
the manufacturer.
Summary of Contents for micromaster 410
Page 1: ......
Page 5: ......
Page 10: ...Safety Instructions Issue 04 02 MICROMASTER 410 Operating Instructions 10 6SE6400 5EA00 0BP0 ...
Page 14: ...Table of Contents Issue 04 02 MICROMASTER 410 Operating Instructions 14 6SE6400 5EA00 0BP0 ...
Page 44: ...3 Commissioning Issue 04 02 MICROMASTER 410 Operating Instructions 44 6SE6400 5EA00 0BP0 ...
Page 56: ...5 System Parameters Issue 04 02 MICROMASTER 410 Operating Instructions 56 6SE6400 5EA00 0BP0 ...
Page 62: ...6 Troubleshooting Issue 04 02 MICROMASTER 410 Operating Instructions 62 6SE6400 5EA00 0BP0 ...
Page 68: ...8 Options Issue 04 02 MICROMASTER 410 Operating Instructions 68 6SE6400 5EA00 0BP0 ...
Page 74: ......
Page 80: ...Index Issue 04 02 MICROMASTER 410 Operating Instructions 80 6SE6400 5EA00 0BP0 ...
Page 82: ...MICROMASTER 410 Operating Instructions 82 6SE6400 5EA00 0BP0 ...
Page 84: ......