6 Troubleshooting
Issue 04/02
MICROMASTER 410 Operating Instructions
58
6SE6400-5EA00-0BP0
6.3 Fault
messages
Fault
Possible Causes
Diagnose & Remedy
Reac-
tion
F0001
OverCurrent
Ø
Motor power (P0307) does not
correspond to the inverter power
(r0206)
Ø
Motor lead short circuit
Ø
Earth
faults
Check the following:
1. Motor power (P0307) must correspond to
inverter power (r0206).
2. Cable length limits must not be exceeded.
3. Motor cable and motor must have no short-
circuits or earth faults
4. Motor parameters must match the motor in
use
5. Motor must not be obstructed or overloaded.
Ø
Increase
the
ramp
time
Ø
Reduce the boost level
OFF2
F0002
OverVoltage
Ø
Overvoltage can be caused either
by too high main supply voltage
or if motor is in regenerative
mode.
Ø
Regenerative mode can be
caused by fast ramp downs or if
the motor is driven from an active
load.
Check the following:
1. Supply voltage (P0210) must lie within limits
indicated on the inverter rating plate.
2. DC-link voltage controller must be enabled
(P1240) and parameterized properly.
3. Ramp-down time (P1121) must match inertia
of load.
NOTE
Higher inertia requires longer ramp times
OFF2
F0003
UnderVoltage
Ø
Main
supply
failed.
Ø
Shock load outside specified
limits.
Check the following:
1. Supply voltage (P0210) must lie within limits
indicated on the inverter rating plate.
2. Supply must not be susceptible to temporary
failures or voltage reductions.
OFF2
F0004
Inverter Over
Temperature
Ø
Ventilation
inadequate
Ø
Ambient temperature is too high.
Check the following:
1. Pulse frequency must be set to default value
2. Ambient temperature could be higher than
specified for the inverter
OFF2
F0005
Inverter I
2
t
Ø
Inverter
overloaded.
Ø
Duty cycle too demanding.
Ø
Motor power (P0307) exceeds
inverter power capability ( r0206).
Check the following:
1. Load duty cycle must lie within specified
limits.
2. Motor power (P0307) must match inverter
power (r0206)
OFF2
F0011
Motor Over
Temperature
I
2
t
Motor overloaded
Check the following:
1. Load duty cycle must be correct
2. Motor temperatur warning level (P0604) must
match.
OFF1
F0041
Stator resistance measurement
failure
Ø
Check if the motor is connected to the
inverter.
Ø
Check that the motor data have been entered
correctly.
OFF2
F0051
Parameter
EEPROM Fault
Read or write failure while saving
non-volatile parameter.
Factory Reset and new parameterization
Change drive
OFF2
F0052
power stack
Fault
Read failure for power stack
information or invalid data.
Change drive
OFF2
Summary of Contents for micromaster 410
Page 1: ......
Page 5: ......
Page 10: ...Safety Instructions Issue 04 02 MICROMASTER 410 Operating Instructions 10 6SE6400 5EA00 0BP0 ...
Page 14: ...Table of Contents Issue 04 02 MICROMASTER 410 Operating Instructions 14 6SE6400 5EA00 0BP0 ...
Page 44: ...3 Commissioning Issue 04 02 MICROMASTER 410 Operating Instructions 44 6SE6400 5EA00 0BP0 ...
Page 56: ...5 System Parameters Issue 04 02 MICROMASTER 410 Operating Instructions 56 6SE6400 5EA00 0BP0 ...
Page 62: ...6 Troubleshooting Issue 04 02 MICROMASTER 410 Operating Instructions 62 6SE6400 5EA00 0BP0 ...
Page 68: ...8 Options Issue 04 02 MICROMASTER 410 Operating Instructions 68 6SE6400 5EA00 0BP0 ...
Page 74: ......
Page 80: ...Index Issue 04 02 MICROMASTER 410 Operating Instructions 80 6SE6400 5EA00 0BP0 ...
Page 82: ...MICROMASTER 410 Operating Instructions 82 6SE6400 5EA00 0BP0 ...
Page 84: ......