3 Commissioning
Issue 04/02
MICROMASTER 410 Operating Instructions
40
6SE6400-5EA00-0BP0
Flow chart Quick Commissioning (Level 1 Only)
1) Motor related parameters – please refer to motor rating plate.
2) Denotes parameters that contain more detailed lists of possible settings for use in specific
applications. Please refer to the Parameter List
P0100 Operation for Europe/N. America
0
Power in kW; f default 50 Hz
1
Power in hp; f default 60 Hz
2
Power in kW; f default 60 Hz
P0305 Rated Motor Current1)
Acceptable Range:
0 - 2 x inverter rated current (A)
Nominal motor current (A) from rating plate
P0307 Rated Motor Power1)
Acceptable Range:
0 kW – 1.0 kW (0 hp – 1 hp)
Nominal motor power (kW) from rating plate.
If P0100 = 1, values will be in hp
P0310 Rated Motor Frequency1)
Acceptable Range:
12 Hz - 650 Hz
Nominal motor frequency (Hz) from rating plate
P0700 Selection of Command Source 2)
(on / off / reverse)
1
Operator Panel (OP)
2
Terminal / Digital Inputs
P1080 Min. Motor Frequency
Sets minimum motor frequency (0-650Hz) at which
the motor will run irrespective of the frequency
setpoint. The value set here is valid for both
clockwise and anti-clockwise rotation.
P1082 Max. Motor Frequency
Sets maximum motor frequency (0-650Hz) at which
the motor will run at irrespective of the frequency
setpoint. The value set here is valid for both
clockwise and anti-clockwise rotation.
P1120 Ramp-Up Time
Acceptable Range:
0 s - 650 s
Time taken for the motor to accelerate from
standstill up to maximum motor frequency.
P1121 Ramp-Down Time
Acceptable Range:
0 s - 650 s
Time taken for motor to decelerate from maximum
motor frequency down to standstill.
P3900 End Quick Commissioning
0
End Quick Commissioning without motor
calculation or factory reset.
1
End Quick Commissioning with motor
calculation and factory reset (Recommended)
2
End Quick Commissioning with motor
calculation and with I/O reset.
3
End Quick Commissioning with motor
calculation but without I/O reset.
P0304 Rated Motor Voltage1)
Acceptable Range: 10 V - 2000 V
Nominal motor voltage (V) from rating plate
P0311 Rated Motor Speed1)
Acceptable Range:
0 - 40000 1/min
Nominal motor speed (rpm) from rating plate
P0010 Start Quick Commissioning
0
Ready to Run
1
Quick Commissioning
30 Factory Setting
Note
P0010 must always be set back to '0' before
operating the motor. However if P3900 = 1 is set
after commissioning this is done automatically.
P1000 Selection of Frequency Setpoint 2)
1
OP frequency control
↑↑↑↑↓↓↓↓
2
Analogue Setpoint
Summary of Contents for micromaster 410
Page 1: ......
Page 5: ......
Page 10: ...Safety Instructions Issue 04 02 MICROMASTER 410 Operating Instructions 10 6SE6400 5EA00 0BP0 ...
Page 14: ...Table of Contents Issue 04 02 MICROMASTER 410 Operating Instructions 14 6SE6400 5EA00 0BP0 ...
Page 44: ...3 Commissioning Issue 04 02 MICROMASTER 410 Operating Instructions 44 6SE6400 5EA00 0BP0 ...
Page 56: ...5 System Parameters Issue 04 02 MICROMASTER 410 Operating Instructions 56 6SE6400 5EA00 0BP0 ...
Page 62: ...6 Troubleshooting Issue 04 02 MICROMASTER 410 Operating Instructions 62 6SE6400 5EA00 0BP0 ...
Page 68: ...8 Options Issue 04 02 MICROMASTER 410 Operating Instructions 68 6SE6400 5EA00 0BP0 ...
Page 74: ......
Page 80: ...Index Issue 04 02 MICROMASTER 410 Operating Instructions 80 6SE6400 5EA00 0BP0 ...
Page 82: ...MICROMASTER 410 Operating Instructions 82 6SE6400 5EA00 0BP0 ...
Page 84: ......