Issue 04/02
5 System Parameters
MICROMASTER 410 Operating Instructions
6SE6400-5EA00-0BP0
53
Analogue I/O (P0004 = 8)
ParNr
ParText
Default
Acc
DS
QC
r0752
Act. input of ADC [V]
-
3
-
-
P0753
Smooth time ADC
3
3
CUT
N
r0754
Act. ADC value after scaling [%]
-
2
-
-
P0757
Value x1 of ADC scaling [V]
0
3
CUT
N
P0758
Value y1 of ADC scaling
0.0
3
CUT
N
P0759
Value x2 of ADC scaling [V]
24
3
CUT
N
P0760
Value y2 of ADC scaling
100.0
3
CUT
N
P0761
Width of ADC deadband [V]
0
3
CUT
N
Setpoint Channel and Ramp Generator (P0004 = 10)
ParNr
ParText
Default
Acc
DS
QC
P1000
Selection of frequency setpoint
2
1
CT
Q
P1001
Fixed frequency 1
0.00
2
CUT
N
P1002
Fixed frequency 2
5.00
2
CUT
N
P1003
Fixed frequency 3
10.00
2
CUT
N
r1024
CO: Act. Fixed frequency
-
3
-
-
P1031
Setpoint memory of the MOP
0
2
CUT
N
P1032
Inhibit reverse direction of MOP
1
3
CT
N
P1040
Setpoint of the MOP
5.00
3
CUT
N
P1070
CI: Main setpoint
755:0
3
CT
N
P1071
CI: Main setpoint scaling
1:0
3
CT
N
P1075
CI: Additional setpoint
0:0
3
CT
N
r1078
CO: Total frequency setpoint
-
3
-
-
P1080
Min. frequency
0.00
1
CUT
Q
P1082
Max. frequency
50.00
1
CT
Q
P1091
Skip frequency 1
0.00
3
CUT
N
P1120
Ramp-up time
10.00
1
CUT
Q
P1121
Ramp-down time
10.00
1
CUT
Q
P1130
Ramp-up initial rounding time
0.00
3
CUT
N
P1131
Ramp-up final rounding time
0.00
3
CUT
N
P1132
Ramp-down initial rounding time
0.00
3
CUT
N
P1133
Ramp-down final rounding time
0.00
3
CUT
N
P1134
Rounding type
0
3
CUT
N
P1135
OFF3 ramp-down time
5.00
3
CUT
Q
r1170
CO: Frequency setpoint after RFG
-
3
-
-
Summary of Contents for micromaster 410
Page 1: ......
Page 5: ......
Page 10: ...Safety Instructions Issue 04 02 MICROMASTER 410 Operating Instructions 10 6SE6400 5EA00 0BP0 ...
Page 14: ...Table of Contents Issue 04 02 MICROMASTER 410 Operating Instructions 14 6SE6400 5EA00 0BP0 ...
Page 44: ...3 Commissioning Issue 04 02 MICROMASTER 410 Operating Instructions 44 6SE6400 5EA00 0BP0 ...
Page 56: ...5 System Parameters Issue 04 02 MICROMASTER 410 Operating Instructions 56 6SE6400 5EA00 0BP0 ...
Page 62: ...6 Troubleshooting Issue 04 02 MICROMASTER 410 Operating Instructions 62 6SE6400 5EA00 0BP0 ...
Page 68: ...8 Options Issue 04 02 MICROMASTER 410 Operating Instructions 68 6SE6400 5EA00 0BP0 ...
Page 74: ......
Page 80: ...Index Issue 04 02 MICROMASTER 410 Operating Instructions 80 6SE6400 5EA00 0BP0 ...
Page 82: ...MICROMASTER 410 Operating Instructions 82 6SE6400 5EA00 0BP0 ...
Page 84: ......