Commissioning
'Technical Ambient Supervision Message' performance check
6
83 | 94
Building Technologies
A6V10209291_h_en_--
Fire Safety
2016-03-03
6 Commissioning
The detectors on the FDnet are commissioned on the control panel. The exact
procedure is described in the control panel documentation.
6.1 'Technical Ambient Supervision Message'
performance check
You cannot test whether the 'Technical Ambient Supervision Message' is
functioning correctly with test devices.
Checking can only take place indirectly:
You must know the current ambient temperature.
Enter the following parameters in the 'SintesoWorks' software:
– A hysteresis range of 5 °C.
– A temperature threshold which is at least 10 °C below the current ambient
temperature.
– Alarming when value falls below threshold
The detector sends a signal to the control panel.
The 'Technical Ambient Supervision Message' is working correctly if the control
panel displays the corresponding message.