4.2.5 Default settings
The default device parameter set is set in the following cases:
Point detector has not been commissioned
Device location cannot be localized (e.g., due to a fault)
When delivered, the default parameter set for the device (sensor mode 0,
parameter set 0) is set in fire detector FDOOTC241.
The following table shows the default device parameter set in the various sensor
modes.
Fire detector FDOOTC241
Default device parameter set
Sensor mode 0 (neural fire detector)
'High Compensation'
Sensor mode 1 (heat detector)
'A1R'
Sensor mode 2 (smoke detector)
'Universal'
Upon commissioning of the fire detection system, the optimum parameter set must
be selected based on the existing risk and the ambient conditions.
After the commissioning of the control panel, the fire detectors are automatically
set to their country-specific basic setting.
You can select and set the parameter sets as follows:
Using the 'SintesoWorks' software
Directly on your fire detection system (only within the same sensor mode)
You will find a description of the exact procedure for selecting and setting the
parameters in the relevant documentation.
Please note the chapter 'Applicable documents'.